Shut down Kubernetes when the UPS goes on battery

The power goes at 02:40. The UPS carries the rack for eleven minutes. Nothing in the cluster knows, so all of it keeps running at full draw until the battery ends and every node loses power mid-write.

Reactor sees the UPS because your UniFi console already does. This guide builds the escalation ladder: shed the cheap load immediately, close a node when the runtime gets short, and stop the things that need a clean stop when it gets critical.

  • Reactor is installed and ReadyInstall.
  • A UniFi UPS is adopted by the same console Reactor polls. The ups, ups.battery, ups.runtime and ups.load keys do not exist otherwise. An Automation matching a key nothing publishes holds its last known matching — false, for one you just created — and reports Ready=False with StateKeyUnavailable naming the key, so it fails visibly rather than silently. A third-party UPS over NUT is a different provider and is not this one.
  • Your workloads are Deployments or StatefulSets in a namespace Reactor can reach. Cross-namespace targets need rbac.clusterWide (the default).

Check the keys are actually there before writing anything:

Terminal window
kubectl -n reactor-system logs deploy/reactor | grep 'key=ups'
# INFO state transition provider=unifi key=ups from= to=online
# INFO state transition provider=unifi key=ups.runtime from= to=ample

1. Shed the cheap load the moment mains goes

Section titled “1. Shed the cheap load the moment mains goes”

The first rung costs nothing to get wrong: workloads that can disappear for the length of an outage without anyone minding.

apiVersion: reactor.robbeverhelst.com/v1alpha1
kind: Automation
metadata:
name: shed-load-on-battery
namespace: media
spec:
when:
provider: unifi
state:
ups: on-battery
actions:
- type: kubernetes.scale
target: { kind: Deployment, name: qbittorrent }
replicas: 0
- type: kubernetes.scale
target: { kind: Deployment, name: plex }
replicas: 0

There is no onExit, and that is the point. With it omitted the reversal policy is Baseline: Reactor records what each workload was set to before it first claimed it — in the annotation reactor.robbeverhelst.com/baseline-replicas, on the workload itself — and restores exactly that when mains comes back. You do not have to remember that Plex runs at 1 and something else runs at 3, and the annotation outlives both the Automation and Reactor. See Reversal and baselines.

ups is debounced at 1 sample, so this fires on the first observation that says on-battery — within one pollInterval, 30s by default. A UPS switching to battery is a switch position, not a measurement, and it does not flap.

2. Escalate on remaining runtime, not on charge

Section titled “2. Escalate on remaining runtime, not on charge”

ups.battery is the obvious escalation key and the wrong one. It reports charge against a threshold, and charge ignores load: 30% at 300W and 30% at 900W are the same value and completely different situations. ups.runtime is the UPS’s own estimate of how long it can carry what is plugged into it right now, bucketed to ample / short / critical against thresholds you set.

That is what a shutdown should match on, and it gets better as the ladder works: every workload rung 1 scaled down raises the runtime the UPS reports for the rest.

apiVersion: reactor.robbeverhelst.com/v1alpha1
kind: Automation
metadata:
name: stop-database-on-critical-runtime
namespace: data
spec:
when:
provider: unifi
state:
ups: on-battery
ups.runtime: critical
actions:
- type: kubernetes.scale
target: { kind: StatefulSet, name: postgres }
replicas: 0
onExit:
- type: kubernetes.scale
target: { kind: StatefulSet, name: postgres }
replicas: 1

Both keys must match — every entry in a state block is an AND. Here onExit is written out rather than left to the baseline, because a database is the one workload where “whatever it was before” is worth stating explicitly instead of inferring.

Where the thresholds come from, and why they are set together rather than one at a time:

ValueDefaultWhat it does
unifi.ups.shortRuntimeSeconds600at or below this, ups.runtime is short
unifi.ups.criticalRuntimeSeconds180at or below this, ups.runtime is critical
unifi.pollInterval30show often the console is polled
unifi.debounce.keys[ups.runtime]2consecutive samples before a change is believed

Two samples at a 30s poll is 60 seconds between the UPS saying critical and Reactor believing it. Against the default 180s threshold that leaves two minutes to get the database down. Lower criticalRuntimeSeconds and that headroom goes with it. Every value is in the chart values reference.

Why two Automations rather than one escalating key

Section titled “Why two Automations rather than one escalating key”

Because a single enum that dropped from on-battery to low-battery would leave the matching state, and leaving a matching state runs the reversal — scaling your workloads back up in the middle of a power failure, at the worst possible moment.

So ups, ups.battery, ups.runtime and ups.load are four independent axes, and escalation is expressed by matching more of them rather than by one key moving. The first Automation stays matched for the whole outage while the second comes and goes underneath it. Power and UPS state keys has the full argument.

If two rungs ever claim the same workload, that is fine and needs no coordination: a shared target sits at the most restrictive level any Automation asked for and comes back only when none of them want it down. See Arbitration.

The endgame of a power cut is a graceful shutdown, not a hard cut. Cordoning a worker on the failing UPS stops new pods landing there, so replacements come up on a node that is still on mains:

apiVersion: reactor.robbeverhelst.com/v1alpha1
kind: Automation
metadata:
name: cordon-worker-on-short-runtime
namespace: reactor-system
spec:
when:
provider: unifi
state:
ups: on-battery
ups.runtime: short
actions:
- type: kubernetes.cordon
target: { kind: Node, name: worker-03 }

A Node is cluster-scoped, so the target takes no namespace — the CRD rejects one at admission rather than looking somewhere that cannot succeed.

Three things to know before adding this rung:

  • It is only worth anything if some nodes are not on the failing UPS. In a homelab where the whole rack is on one UPS, cordoning buys nothing: there is nowhere else for a pod to go.
  • It needs a permission Reactor does not otherwise ask for. --set rbac.allowNodeActions=true creates a ClusterRole even in a namespace-scoped install, and grants get and patch on nodes — and Kubernetes cannot narrow patch to one field. Without it, the Automation reports the node as unreachable and names the value to set. The plain manifest bundle does not offer it at all.
  • Cordoning moves nothing that is already running. There is deliberately no kubernetes.drain: an eviction cannot be un-evicted, so it has no level to arbitrate and no reversal to declare, and in a three-node cluster the evicted pods go Pending rather than anywhere useful. Why there is no drain.

Omitting onExit here restores the baseline, which includes leaving a node cordoned that you had already cordoned by hand — recorded in reactor.robbeverhelst.com/baseline-unschedulable before Reactor touched it.

Terminal window
kubectl -n media get automation
# NAME PROVIDER MATCHING SUSPENDED READY AGE
# shed-load-on-battery unifi true false True 6d
Terminal window
kubectl -n media describe automation shed-load-on-battery
Type Reason Age From Message
---- ------ ---- ---- -------
Normal StateEntered 42s automation ups moved from "online" to "on-battery", so the condition started holding
Normal TargetHeld 42s automation Deployment/media/qbittorrent held at 0 replicas
Normal TargetHeld 42s automation Deployment/media/plex held at 0 replicas

The workload itself says who is holding it down and what it was:

Terminal window
kubectl -n media get deploy qbittorrent -o jsonpath='{.metadata.annotations}'
# {"reactor.robbeverhelst.com/baseline-replicas":"1",
# "reactor.robbeverhelst.com/claimed-by":"media/shed-load-on-battery",
# "reactor.robbeverhelst.com/claimed-at":"2026-08-15T02:40:11Z"}

And when mains returns:

Normal StateExited 8s automation ups moved from "on-battery" to "online", so the condition stopped holding
Normal TargetReleased 8s automation Deployment/media/qbittorrent released; no automation claims it any more

TargetHeld and TargetReleased are raised only when a write actually happened. A target already at the right value produces nothing, so a long outage is three Events and not one every fifteen seconds.

Likely, if your gateway is on the same UPS. Reactor holds the last known state and keeps acting on it — it does not treat losing sight of the UPS as the outage ending, because that would scale everything back up in the middle of one. You get Ready=False with StateKeyUnavailable (a key vanished) or ObservationStale (the console stopped answering entirely, on an install that set unifi.maxObservationAge), and the claims stay exactly where they were. When Reactor cannot see.

  • It does not shut down machines. Nothing here powers off a node or a NAS. Cordoning closes a node to new work; the shutdown itself is still yours, and a notification.* action telling you to run it is the honest shape — see Get told when the WAN fails over for the setup, which is identical for a UPS message.
  • It does not stop a running Job. Suspending a CronJob is a separate rung and stops only new Jobs — Suspend scheduled work during an outage.
  • It does not switch a UPS outlet. Reactor reads outlet.<n> and never writes one, so “cut power to outlet 3” is not part of any plan you can write today. (Toggling a single outlet by hand on a UniFi UPS 2U moved only that outlet, and relay_group turns out to separate battery-backed outlets from surge-only ones rather than naming a switching bank — but no write action has shipped, and #23 is where that is decided.)
  • It cannot help a workload an HPA drives. Reactor declines those rather than fighting — Run alongside a HorizontalPodAutoscaler.

ups.runtime is derived from the UPS’s timeToRemain field, and its unit is inferred to be seconds from a single observation on a UPS that was not discharging. Nothing in Reactor depended on it before this key existed. The ups key itself is verified against a real capture; the runtime thresholds are not verified against a real discharge.

So: put the ladder in with spec.dryRun first, pull the mains lead, and watch what ups.runtime actually reports as the battery drains against a clock. #7 has the procedure, and confirming it is fifteen minutes that would settle the key for everybody.